Xantrex Technology TV Cables Link 20 User Manual

Link 20  
Owner's Manual  
Xantrex  
Link 20  
Battery Monitor  
 
LINK 20 INTRODUCTION  
Congratulations! You have purchased the world's only Dual Watchtm battery monitor.  
In order to understand, use, and install it, PLEASE read this manual. It provides important  
information. Please contact us with suggested improvements. For Link 20 installation,  
operation, warranty support, and repair questions, please contact Xantrex.  
The Link 20 provides instrumentation of two banks of batteries. The Link 20 does not  
controlaninverter/charger.ForinstallationsinvolvingaFreedomInverter/Chargerandtwo  
batterybanks, XantrexrecommendstheLink2000. IfaFreedomInverter/Chargerandone  
battery is anticipated, Xantrex recommends the Link 1000. For instrumentation of a single  
battery bank with no inverter/charger controls, the Link 10 is ideal.  
Thissymbolisusedtopointoutveryimportantsectionsofthismanualortoindicate  
items that may need to be changed through Set Up routines. Please take the time to read  
these sections.  
The following warnings must be considered during the installation of the Link 20.  
Failure to read and follow these special notes can lead to damage to the Link 20 or other  
electricalequipment.  
POWER CONNECTION WARNINGS  
1.  
When installing your Link 20, make all shunt and ground connections BEFORE  
applying power to the unit.  
2.  
The wires connecting the battery to the dual shunt, and from the dual shunt to your  
system ground, will carry large current. Size the wire appropriately. Large batterry  
banks contain enough energy to start a fire if improperly sized wire is used.  
3.  
Disconnect all charging sources during the installation process.  
IMPORTANT BATTERY FACTS  
1.  
2.  
An amp hour (Ah) is 1 amp of current flowing for one hour, or 2 amps for  
1/2 hour, or 4 amps for 1/4 hour, and so on.  
Many batteries designed for deep-cycling service are rated at their 20-hour rate.  
This means a 12-volt, 100 amp-hour battery will sustain 5 amps for 20 hours before  
its voltage under load drops to 10.5 volts. A 12 V lead-acid battery which will not  
maintain 10.5 volts under load is considered "dead"—it's completely discharged.  
3.  
Our Mid-Capacity Rule says discharging more than 50% of a battery's capacity  
shortenslife.Chargingmore than85%takes too longwith anengine-drivencharging  
system.So,35%ofthebatterycapacityisallthatisnormallyavailable.Ifyouregularly  
need100amphoursofenergy,yourbatterycapacityshouldbeabout300amphours.  
3
 
FRONT PANEL OF YOUR LINK 20  
The exclusive Dual Watchtm light bars give you battery state-of-charge information at a  
glance. It's easy to train your whole crew, even the kids, to turn off loads and start charging  
T
when the light bar shows two yellow lights. When the light bar is green, you've got plenty  
ofenergy.Withoneflashingredlight,you'dbetterchargeorstarthuntingforjumpercables!  
This light bar shows Battery 1  
This light bar shows Battery 2  
i4.25  
When BAT 2 is pressed,  
the display numbers are  
for battery 2.  
SEL selects the units  
being displayed: volts,  
amps, amp hours, Time  
of Operation Remaining.  
When BAT 1 is pressed,  
the display numbers are  
for battery 1. The light  
above each button re-  
minds you which battery  
you're looking at.  
SET picks from among  
choices. You'll SET a  
battery size from a list  
of choices when you  
first install your Link 20.  
4
 
USING YOUR LINK 20  
STATUS LIGHTS  
These green lights tell you  
what units are displayed.  
Volts is the electric potential to do work. Voltage is useful to  
assess the approximate state-of-charge and to check for proper  
charging. Examples: An at-rest, fully charged battery will show  
about 12.8 V. A 20-hour rated battery is 100% discharged  
when it reaches 10.5 volts with a 20-hour rated load applied.  
Typical charging voltages may range from 12.9 to 14.9 volts.  
Amps is the present flow of current into (or out of) the battery.  
For example, a refrigerator may draw 6 amps of current. This  
is displayed as - 6.0 (6 amps are being consumed from the  
battery). Discharge is shown as a negative number. Charging  
is shown as a positive (unsigned) number.  
Amp hours (Ah) consumed represents the amount of energy  
removed from the battery. When a 10-amp load is on for one  
hour, 10 amp hours are consumed. If you started this discharge  
with a full battery, your Link 20 will show -I0 in the  
display. During charging the Link 20 compensates for charging  
inefficiency and counts back up toward 0.  
Time is an estimate of how many hours the battery will sus-  
tain a load before it reaches a settable discharge floor. The  
estimate may be based on the instantaneous load or averaged.  
Four-minute load averaging is the default. During charging  
the Time display reads CCC , indicating the battery is charg-  
ing. When charging, amps is a positive number.  
For the TIME function to operate correctly, you must correctly enter your battery  
capacity, type, and check that an appropriate Peukert Exponent has been selected through  
the SET UP routines.  
5
 
READING THE LIGHT BARS  
Above the Link 20 numeric display  
are two light bars, each with four  
lights. They show you battery state-  
of-charge at a glance.  
Four green lights means your battery is nearly  
full (80–100% charged).  
A single flashing red light means it's nearly discharged.  
Light bar scaling is independently settable. As the Link 20 comes  
from the factory, it is set to show a flashing red light whenever your  
battery is more than 80% discharged (20% charged). The default  
setting usually indicates enough energy remains with two yellow lights  
showing to start an engine-driven charging source. If desired, you  
may scale the light bar to show a flashing red light when your battery  
is more than 40% discharged, however, this is not recommended. To  
set a discharge floor other than 100%, see page 19, Function F09.  
EMPTY Symbol  
FULL Symbol  
Percent Full  
Default  
Optional  
100%  
100%  
80–99.9  
60–79.9  
40–59.9  
20–39.9  
0–19.9  
90–99.9  
80–89.9  
70–79.9  
60–69.9  
50–59.9  
100% floor 50% floor  
TheLightBarsoperateonrate-correctedamphours.Ifyouhaveheavilydischarged  
a battery bank, the light bar may tell you to charge before you would normally make that  
decision based on the amp-hour display. See High Discharge Rates, page 26.  
6
WE RECOMMEND: Charge your batteries when the Light Bars tell you to!  
 
LINK 20 BATTERY MANAGEMENT  
SIMPLE BATTERY MANAGEMENT RULE:  
Recharge When the Battery is 50% Discharged!  
The Link 20 is a guide to the battery's state of charge. Our Mid-Capacity Rule  
says you should begin charging when your Link 20 shows that 50% (or more) of battery  
capacity has been consumed. In marine and RV systems, which are trying to minimize  
chargingtimewithanengine-drivenalternatororgenset,thebatteryisnormallychargedonly  
tothe85%level.Thismeansonly35% ofthebatterycapacityisactually availableforuse.  
The Mid-Capacity Rule is a very conservative approach to battery use. Occasion-  
ally discharging a battery more deeply is perfectly acceptable. The Mid-Capacity Rule  
is intended as a design and operating guideline, not a law which must be obeyed without  
exception.  
We recommend synchronizing your Link 20 to the 100% charged level of the  
battery. You should begin recharging when 50% of the your battery capacity has been  
consumed.  
When recharging from an engine-driven alternator or generator supplied  
battery charger you do not need to charge until the meter counts back up to 0 amp  
hours consumed. You may end charging even though the final 15% of battery capacity  
has not been restored. Later, when you are able to charge for a long period of time, the  
remaining amp hours consumed will be replaced.  
Periodic conditioning or equalizing removes any negative amp hours that are not  
replaced during normal charging.  
OVERCHARGEAMPHOURS  
If the batteries are 100% charged and the Link 20is in sync, overcharge amp hours  
aredisplayedasapositiveamp-hournumber.Someaccumulationofoverchargeamphours  
isnormalwithsystemscontinuouslyconnectedtoacharger.Forexample,a100Ahbattery  
at Float voltage will normally have about 0.1 amp flowing into it. This means you would  
expect about 2.4 amp hours of overcharge to accumulate each 24 hours. If your battery  
system is larger, proportionately more current flows and amp hours accumulate.  
Withaconstantvoltagechargingsystemsetat14.2volts,asmuchas1ampofcurrent  
maybeflowingallthetimeevenafterthebatteryhasreachedthe chargedparameters.This  
causesasmalloverchargeamp-hourreadingtoappearintheAhdisplay.Whendischarging  
begins, these overcharge amp hours are erased and the Link 20 resets to zero and begins  
to report amp hours consumed.  
Prolongedhighvoltageappliedtoafullychargedbatterywillprobablycausegassing.  
So, if you see a large amp-hour overcharge occuring daily, consider it a warning to check  
your system. It could indicate that you are destroying your battery by overcharging.  
Whenyouequalizeyourbatteries,youwillaccumulatesomeoverchargeamphours.  
This is normal and keeps the Link 20 synchronized with the battery state of charge.  
7
 
BATTERYCAPACITYTESTING  
Your Link 20can be used to conduct periodic capacity tests that tell you the actual  
amount of energy your batteries can store. A capacity test should start with a battery that  
has been properly charged and equalized. The objective is to find the maximum available  
capacity.  
Many times, deep-cycle battery capacity is stated as a 20-hour discharge rate. A  
100 Ah battery will provide 5 amps for 20 hours. At discharge rates above 5 amps, the  
batterywillnotsupply100Ah.Forexample:Ifyouaredrawing100ampsoutofthebattery  
it will last less than half an hour. Consider the following table:  
CAPACITY AT VARIOUS DISCHARGE RATES  
(As a percent of 20-hour rate)  
Hours to Discharge Capacity (percent of rating)  
20  
10  
5
3
1
100%  
84%  
67%  
56%  
47%  
To test battery capacity, reset amp hours to zero. Then turn on a load that draws  
approximately5%oftheexpectedbatterycapacity.MeasurethecurrentwithAmpsdisplay.  
The load should be constant, such as incandescent lighting. Now put the Link 20 in the  
Voltsdisplaymode.Whenthebatteryvoltagedropsto10.5volts(or21voltsifyou'retesting  
a24Vsystem), hopefullyabout20hourslater, turnoff theload andlookattheamp-hours  
display on your Link 20. The amp hours displayed is your actual battery capacity.  
If less than 20 hours passed before the battery voltage fell to 10.5 V you can still  
determinethecapacitywithsomearithmetic. Forexample:Assumea12Vbatteryratedat  
100 Ah. Apply a 5-amp load. Suppose it only took 10 hours for the voltage to reach  
10.5 volts. The Link 20 would display -50 Ah. This is the 10-hour capacity. Dividing 50  
by84% (10-hourrate) fromthetableabove,youdeterminethattheactual 20-hourcapacity  
is about 60 amp hours. You could repeat the test at 5% of the tested capacity (3 A) to verify  
the actual capacity.  
USING YOUR INVERTER  
TO TEST BATTERY CAPACITY  
Yourinvertermightbethetypewhichmakestesting batterycapacityeasy.First,fully  
charge (equalize if necessary) the battery to be tested. Use a load like incandescent lights  
runningontheinverterwhoseamperageconsumptionis5%orlessofthebatterycapacity.  
Manyinverterswillshutdownonlowvoltagebelowabout10.2V.Whentheinvertershuts  
down, read the number of amp hours that have been consumed from the battery. If it is not  
close to the expected number use the procedure outlined above to estimate the capacity.  
CAUTION! Be sure to completely recharge your battery after a discharge test.  
8
 
SYNCHRONIZINGTOYOURBATTERY  
A charged battery has zero amp hours removed. Synchronizing your Link  
20 to read zero when the battery is charged ensures that you always know the net number  
of amp hours removed.  
There are two ways to synchronize your Link 20:  
1) Install the Link 20 on a fully charged battery and it will be in sync.  
2) If the Link 20 is installed on a partially charged battery, simply charge until  
thechargedparametersaremet.TheDualWatchlightbarsshowthisbyflashingtheright  
greenlights.TheLink20willbegincountingupandwilldisplayoverchargingamphours  
as a positive number. When the battery is fully charged, turn off the charging source.  
When discharging begins the Link 20 resets amp hours to zero, starts counting down,  
and is in sync.  
If the Link 20 should ever get out of sync with the battery state of charge it must  
be resynchronized. The best way is to be sure the battery is discharged at least 10% of the  
declaredbatterycapacityandthenrechargeuntilthechargedparametersaremet.Whenthe  
next discharge cycle begins, the amp-hour display should reset to zero.  
Remember: Periodic controlled extra charging ensures that the Link 20 remains  
in sync with the battery's state-of-charge.  
9
 
SETUP PROCEDURES  
Your Link 20 comes with default  
valueschosentoworkwithmostsystems.  
Normally the only values that need to be  
changed are the battery capacity, battery  
type(liquidorgelled),andhighdischarge  
rate compensation (Peukert) exponent.  
Please be sure you understand each  
function before changing the factory  
default values outlined below.  
i4.25  
Holding the SET button for five seconds accesses the Set Up and Advanced  
Functions. The display will read SEL. If you press SEL once, you will display the first  
Setupvariable:ChargedVoltage.PressingSELrepeatedlywillstepthroughmorevariables:  
Charged Current, battery amp hour capacity, and averaging period for Time Remaining.  
Corresponding status lights come on for each.  
If you continue pressing SEL, you will step through functions named in small text  
beloweachofthelightsontheBattery1LightBar.Some functionshavemultipledisplays.  
These are described in later pages devoted to RESET, DATA, and LOCKing of your  
meter. The next (right) battery status light indicates you've entered the Advanced  
FUNCtions area (see page 17).  
When a desired variable or function is displayed, pressing the SET button will  
displaythe presentvalueofthefunction. PressingSETagainwilldisplaythenextchoice.  
If you hold the SETbutton, the display begins scrolling. When the desired value appears,  
release the button. If the button is held down longer, the display will increment to the end  
of its range, then roll over to its minimum value and continue to scroll.  
Ifthissoundscomplicated, relax!It'snot. Onceyougothroughitafewtimes, itwill  
become second nature. On the next page, we'll go through this again step-by-step.  
FACTORY DEFAULT VALUES  
Monitoring Functions:  
Charged Voltage  
= 13.2 volts for 12-volt systems  
= 26.4 volts for 24-volt systems  
= 2% (of battery capacity, 4 amps @ 200 Ah)  
= 200 Ah  
= 95% (Charge Efficiency Factor)  
= 70 oF  
Charged Current  
Battery Capacity  
CEF  
Ambient Temp.  
Battery Type  
= #1 (Liquid cells)  
Peukert Exponent  
= 1.25  
10  
 
USING SET AND SEL BUTTONS  
Pressing and holding the SET button for five seconds enters the Setup and  
Advanced Functions modes. The word SEL appears in the display, prompting you to press  
the SEL button to choose what function you want to SELect.  
PRESS BAT 1OR BAT 2TO PICK THE BATTERY YOU WISH TO SET UP.  
Pressing SEL chooses a variable or function. The Setup mode always begins at  
the  
(Volts) function. Each press of the SEL button scrolls to the next item. When  
avariableorfunctionisselected, itscorrespondinglightandpresentvalueisdisplayed. To  
change a variable, press the SET button until the value appears that you wish. The order  
displayed and brief descriptions are below.  
LIGHT  
DESCRIPTION  
ChargedVoltage (Batterymustbeabovethisvoltagetobeconsidered"full.")  
Charged Current % (Charging current in amps must remain below this  
percentage of battery capacity to be considered full.)  
Battery Capacity in amp hours  
Time interval over which current is averaged for Time Remaining function.  
Each light will come on in sequence.  
Advanced Functions. See page 16.  
Locks out SET button and Advanced Func-  
tions. See page 24.  
DisplaysCEF,#CEFRecalc's,AverageDepth  
of Discharge, Deepest Discharge.  
Resets amp hours and allows reset of every-  
thing to factory default values. See page 22.  
Now let's SET UP your system. We'll explain Charged  
Voltage, Charged Current Percentage, Battery Capacity, Time  
of Operation Remaining averaging, and set an appropriate rate  
compensation (Peukert) exponent.  
11  
 
TheC WHEN TO SET UP AND  
The Link 20 depends on correctly set Charged Parameters to stay in sync with  
battery state-of-charge, to automatically reset to zero, and to automatically calculate the  
Charging Efficiency Factor of your battery. The two numbers which define Charged  
Parameters are Charged Voltage and Charged Current Percent.  
What these Charged Parameters mean is simply this: If you charge a battery above  
a given charging voltage and hold it there until the charging current drops below a few  
percent of battery capacity, the battery is effectively FULL. Although you could continue  
charging, once voltage is held high and charging current drops to a few percent, any  
additional energy going into the battery will be turned into heat.  
Basedonextensivestudies,wehaveselectedadefaultChargedVoltageof13.2volts  
and a Charged Current of 2% of declared battery capacity. This means a 200 Ah liquid cell  
batteryheldover13.2voltsuntilchargingcurrentdropsbelow4ampsiseffectivelyfull. (4  
amps is 2% of 200 amp hours.) Once your system is able to fully recharge your battery, we  
can then calculate battery efficiency when five conditions are met:  
CONDITIONS TO RESET TO ZERO  
1. Discharge 10% of declared battery capacity to trigger algorithm.  
2. Recharge until kWh becomes a positive number.  
3. The voltage must be above the Charged Voltage Parameter.  
4. The current must be below the Charge Current % Parameter.  
5. Conditions 3 & 4 must be met for 5 minutes (1 min. for AE [F05] mode).  
If your battery voltage is other than 12 or 24 V, you must set up an appropriate  
Charged Voltage.  
If the charged parameters are not set correctly, the Link 20 will never recalculate  
the CEF. If you accumulate negative amp hours, check your charged parameters.  
Please consider changing only the battery capacity unless your system falls into one of the  
followingcategories:  
1)  
Battery chemistry other than lead acid.  
12 Volt NiCad (and NiFe) systems would normally use 15.5 to 15.7 as the Charged  
Voltage. See your battery specifications for guidance. The Charged Current % can  
probably stay at 2% of declared battery capacity.  
2)  
3)  
Charging normally ends before current drops below 2%.  
If the charging system is normally shut down before charging current drops below  
2%, the Charged Current % will have to be changed.  
Your system operates at extremes of temperature. For example, below 45 °F  
or above 90 °F.  
12  
 
HOW TO SET  
Your Link 20 automatically selects an appropriate charged voltage for 12-volt  
liquid and gel cells when you set battery type. (We'll cover setting battery type on page  
19). If you operate a 24-volt system, or if extremes of temperature are involved, here's  
how to change charged voltage:  
1.  
2.  
Press SET for five seconds. SEL will appear in the numeric display.  
Press SEL once.  
The  
light will come on and 13.2 will  
appear in the numeric display.  
3.  
Press and hold SET.  
The numeric display will move up in 0.1 volt  
steps until 50.0 volts is displayed. The  
display will then "wrap around" and  
start counting up from 8.5 volts. Stop at the  
desired voltage.  
4. After 10 seconds, the displayed  
setting is stored in memory and  
normal operation resumes.  
HOW TO SET  
The Link 20 is factory set to use 2% of battery capacity as Charging Current  
Percentage. If you normally end charging before 2% is reached, or use a very large  
battery bank, such as might be encountered in an alternative energy installation, a different  
value may be appropriate. Here's how to change it:  
1.  
2.  
Press SET for five seconds. SEL will appear in the numeric display.  
Press SEL twice.  
The  
light will come on and 2 will  
appear in the numeric display.  
3.  
Press and hold SET.  
The numeric display will move up in 1 percent  
steps until 7 percent is displayed. The  
display will then "wrap around" and  
start counting up from 1 percent.  
4. After 10 seconds, the displayed  
setting is stored in memory and  
normal operation resumes.  
13  
 
HOW TO SET (BATTERYCAPACITY)  
The first time you apply power to a Link 20, it assumes you have two banks of  
200 amp-hours battery capacity each. 200 amp hours is the factory default capacity. If  
your battery capacity is different (and it probably is) you must change the declared  
battery capacity. Before you try to set battery capacity, you'll need to know what your  
battery (or battery bank) should deliver.  
The surest way is to ask for the manufacturer's 20 hour rating. If that's missing, remem-  
ber that for 12-volt liquid cells, a Group 24 battery has about 85 amp hours, a Group 27  
size has about 100 amp hours, a Group 30 has about 130 amp hours, while 4Ds hold  
about 160 amp hours and the heavier 8D is generally about 220 amp hours. Gel cells  
generally hold about 15% fewer amp hours for a given size. A Group 27 case gel cell  
stores about 85 amp hours.  
If you use two batteries in parallel, as a single bank, use twice the amp-hour capacity of a  
single battery. For three batteries in parallel, use three times the amp-hour capacity. If  
you parallel batteries, use the same size and same age batteries. If you use two batteries  
in series, such as two 6 V golf cart batteries, use the amp-hour capacity of one battery.  
For example, if you have three 12-volt Group 27 batteries in parallel, you would use  
(100 Ah x 3) 300 Ah for your battery capacity. Two Trojan T-105 6-volt golf cart  
batteries in series would use the factory default 200 amp hours for capacity.  
If you need to change the default setting, here's how you do it:  
1. Press SET for five seconds.  
2. Press SEL three times.  
SEL will appear in the numeric display.  
The light will come on and 200 will  
appear in the numeric display.  
3. Press and hold SET.  
The display will move in 20 amp-hour steps over  
100amphoursofcapacity. 1amp-hourincrements  
are shown from 20–40 amp hours of capacity, 5  
amp-hour steps from 40–100 amp hours capacity.  
If you continue to hold SET, after four increments  
the display scrolls faster. When the value you want  
appears, release the SET button. If you overshoot  
your capacity you will have to scroll all the way to  
1980amphoursafterwhichthedisplaywillrollover  
and begin scrolling up starting from 20 amp hours.  
4. After 10 seconds, the displayed  
setting is stored to memory and  
normal operation resumes.  
14  
 
HOW TO SET  
There are four different ways the Link 20 can approximate time of operation  
remaining. You may select present consumption level, a four-minute rolling average, a  
16-minute, or a 32-minute rolling average. Which method is best for you depends on  
yourinstallation. Mostinstallationswillfindthefour-minuteaverageappropriate.  
1.  
2.  
Press SET for five seconds. SEL will appear in the numeric display.  
Press SEL four times.  
The  
light will come on and 001 will  
appear in the Link 20 numeric display.  
3.  
Press and hold SET.  
The numeric display will move up in 1 unit  
steps with choices of:  
Instant:  
4-Minute Avg:  
Display: 000  
Display: 00I  
16-Minute Avg: Display: 002  
32-Minute Avg: Display: 003  
4. After 10 seconds, the displayed  
setting is stored in memory and  
normal operation resumes.  
INTRODUCTION TO RATE COMPENSATION  
AND THE PEUKERT EXPONENT  
Your Link 20 shows true amp hours consumed in the numeric amp-hour display.  
However, the light bar above it shows how much of the available battery capacity has  
been consumed. You may experience times when the light bar shows more than 60% of  
capacity consumed, yet according to the numeric display less than half of the battery  
capacity has been consumed. How can this be?  
In 1897 a scientist named Peukert demonstrated that as you discharge a battery  
more quickly, its effective size temporarily decreases. A battery is considered fully dis-  
charged when it is no longer able to maintain 10.5 volts under load. As you'll see in the  
following table showing the effect on a typical liquid cell battery, the faster the discharge  
rate, the smaller its effective capacity:  
Hours to Discharge  
Capacity as percent of 20-hr rating  
20  
10  
5
2
1
100%  
84%  
67%  
56%  
47%  
Inotherwords,a100amp-hourbatterydischargedcompletelyinonehourwillonlysupply  
47 useful amp hours.  
15  
 
HOW TO SET UP FUNCTIONS  
When the FUNC light is on,  
you can access Advanced  
Functions of the Link 20.  
Thevaluesforeachfunction  
are changed using the SET  
and SEL keys.  
i4.25  
1) Hold down the SET button until the numeric display says  
                                                                                                                         
SEL.  
                                                                                                                         
                                                                                                                           
                                                                                                                           
                                                                                                                             
                                                                                                                             
2) Now press the SEL button 11 times F0i will appear in the display. You are now at  
F01 in the FUNCtion mode.  
3) Press SEL again until the function you wish to set up appears.  
4) Press the SET button to show the current value of the function you have selected.  
5) To change the function value, press SET. The display will scroll through the range  
of available values. Stop scrolling when the value you wish appears in the display.  
6) If you are only changing one function, simply leave the unit alone and in five seconds,  
the display will return to normal and the choice you have made for the function  
selected will be stored in memory.  
7) If you wish to set up other functions, press the SEL button right away after making  
your selection in Step 5. You'll now scroll on to the next function, which can be  
changed the same way. When you have made all the changes desired, simply leave  
the unit alone for five seconds and the values will be memorized and the display  
returned to normal operation.  
FUNCTIONS TABLE  
The above section gave you the general approach to changing an Advanced Func-  
tion setting. Now, we'll go through each of the Advanced Functions and explain  
what each does and how you may wish to use it. If you ever get "lost" and want to  
restore all factory default settings, simply follow the RESET procedure on page 25.  
F01 - AUTO DISPLAY SCANNING  
DEFAULT = OFF  
RANGE: OFF, ON  
Automatically scans through the major displays, volts, amps, amp hours, and Time  
of Operation remaining. Each value is displayed for four seconds.  
Scanning applies only to the battery selected with the BAT button.  
16  
 
F02 - DISPLAY SLEEP  
DEFAULT: ON  
RANGE: ON, OFF  
Turns off all lights on the front panel except for the light bars after 10 minutes of no  
front panel key presses. Touching any button "wakes up" all displays.  
F03 - SET AMBIENT BATTERY TEMPERATURE  
DEFAULT = 70 °F  
RANGE = 30–120 °F  
STEP = 10 °F  
The Link 20 default ambient temperature setting is 70 °F. The ambient temperature  
may be set in 10 °F increments. The setup procedure is the same as previously described.  
The ambient temperature setting adjusts effective battery capacity lower when colder  
and larger when warmer. Adjust the temperature to best reflect the battery temperature  
during discharge. High temperatures are destructive to batteries. If your batteries are  
regularly subjected to temperatures above 100 °F you should relocate them or supply  
forced fresh air ventilation.  
IMPORTANT!  
Your Link 20 incorporates a precision volt meter. This may  
be used to check that your charging sources are set to the  
correct Accept and Float voltage values for your battery  
temperature. Refer to the following table.  
If your batteries are operating significantly (0.3 Volt)  
different from the values below, you are likely undercharging or  
overcharging. This will result in degraded performance of your  
system and shortened battery life.  
TEMPERATURE COMPENSATION TABLE  
TYPE #1=WET  
TEMP °F °C ACCEPT FLOAT  
12.5  
TYPE #2=GELLED  
ACCEPT  
13.9  
FLOAT  
13.3  
120  
110  
100  
90  
49  
43  
38  
32  
27  
21  
16  
10  
5
13.4  
13.6  
13.8  
14.0  
14.2  
14.4  
14.6  
14.8  
15.0  
15.2  
12.7  
12.9  
13.1  
13.3  
13.5  
13.7  
13.9  
14.1  
14.3  
14.0  
13.4 Caution above this temp.  
14.1  
13.5  
14.2  
13.6  
80  
70  
60  
50  
40  
30  
14.3  
13.7  
14.4  
13.8 <"Average" settings  
14.5  
13.9  
14.6  
14.0  
14.7  
14.8  
14.1 Caution below this temp.  
14.2  
-1  
17  
 
F04 - DISPLAY AMP HOURS OR KILOWATT HOURS  
DEFAULT OFF = Ah DISPLAY MODE  
ON = kWh DISPLAY MODE  
WhenthisfunctionisselectedtheAh displayshowskilowatthours. Kilowatthours  
are used internally by the Link 20 to determine if 100% of the energy consumed from  
a battery returned during charging. A recalculation of theCEF is not permitted unless this  
counterisgreaterthan0.00kWh. ThiscountercountsdownduringdischargeandthekWh  
consumedaredisplayedasa negativenumber. Duringchargingitcountsbackupwith100%  
efficiency.CEFrecalculationispreventeduntil thekWhcounterisapositivenumber.This  
prevents premature CEF recalculation and Ah reset. Kilowatt hours is a very precise  
measurement of energy removed from or returned to your battery banks.  
F05 - ALTERNATIVE ENERGY MODE  
DEFAULT: OFF  
ON: BATTERY/SOURCE MONITORING MODE  
This function selects between the normal two-battery monitoring mode and the  
battery/sourcemonitoringmode.WhenthismodeisOFF, themeterworksasatwo-battery  
monitor as described elsewhere in this manual.  
SOURCE MONITORING: When this mode is ON, the BAT 1 position works normally,  
showingenergyflowinginto(oroutof)Battery#1.TheBAT2voltandampsdisplays report  
the charging source voltage and current. The BAT 2 Ah display reports cumulative amp  
hours from one (or more) charging source(s). The BAT 2 Ah display will count up to 1999  
and then roll over to 0 and continue to count up. This is the total number of amp hours  
suppliedsincethemeterwaspoweredup(orRESET). Youmayalsousethekilowatthours  
display (see previous function, F04). The BAT 2 Time display will read CCC. The BAT 2  
CEF is set to 100% and is displayed as 100.  
CHARGED PARAMETERS: Also, when this mode is ON, the time necessary to meet  
the Charged Parameters is reduced from five minutes to one minute. This is useful if your  
alternativeenergyinstallationusessolarpanelsandyouhavecloudsperiodicallyobscuring  
thearraycausingyourchargingtobeintermittent.It'salsousefulifyou'reusinganON/OFF  
(high-low voltage set point window) controller. If you're using this type of controller, you  
may wish to increase Charged Current % to 3% or 4% of Battery Capacity.  
(See How to Set  
on page 13.)  
F06 - MANUALLY SET CEF (Not Recommended)  
DEFAULT OFF = AUTO RECALCULATION OF CEF  
DISPLAY = A95  
RANGE = 65–99 STEP = 1  
Allows manual setup of CEF (Charge Efficiency Factor). Default display A95  
indicates automatic CEF recalculation feature. Returning to A95 from a user declared CEF  
turnstheautomaticCEFfeaturebackon.Ifauser-setupCEFhasbeenselecteditwillappear  
as a Uxx in the DATA mode.  
18  
 
F07 - SET TEMPERATURE COEFFICIENT  
DEFAULT = 0.5 RANGE = 0.1–1.5  
STEP = 0.1  
Thisfactorcompensatesforcapacitychangewithtemperature. Typicalvalue 0.5%  
Capacity/°C. This coefficient must be supplied by the battery manufacturer. The default  
value is typical for lead acid liquid or gelled batteries. Normally this value is not changed.  
F08 - SET PEUKERT'S EXPONENT  
DEFAULT = 1.25*  
RANGE = 1.0–1.50  
STEP = 0.01  
Sets the exponent for Peukert’s equation. A setting of 1.0 defeats Peukert's  
calculation. Properly setting Peukert's exponent ensures an accurate display of time  
remaining.Seepage26foradiscussionofPeukert'sequationandtypicalvaluesforvarious  
batteries. *Default for liquid electrolyte batteries (F10 set to Type 1). When F10 is set to  
gelled electrolyte batteries (F10 set to Type 2), a default exponent of 1.11 is used.  
F09 - LOW BATTERY DISCHARGE FLOOR  
DEFAULT = 100%  
RANGE: 50%–100%  
STEP: 5%  
Your Link 20 allows you to declare the discharge floor used for meter calculations.  
An independent discharge floor may be selected for each battery bank. The display  
floor will be applied to the battery bank selected (BAT 1 or BAT2) at time this func-  
tion is invoked. As supplied by the factory, the discharge floor is 100% of amp-hour  
capacity, corrected for high discharge rates. With the discharge floor to 100%, the  
TIME remaining display essentially reports TIME to "dead battery." If you change  
the discharge floor to 50%, you would essentially see the TIME "till the battery is  
50% discharged." This is when charging should begin to conform to our "Mid  
Capacity Rule."  
CAUTIONS: If you discharge below the discharge floor, partially charge, but remain  
below the discharge floor, the TIME remaining display will continue to read zero. The  
TIME display will not show meaningful readings until you have recharged above the  
discharge floor you have set. Also, remember that the light bar and TIME remaining  
displays are run on rate compensated (Peukert equation corrected) amp hours.  
F10 - BATTERY TYPE  
DEFAULT = 1 RANGE: 1 = WET (LIQUID) ELECTROLYTE  
2 = GELLED ELECTROLYTE  
This function declares your choice of liquid or gelled electrolyte batteries. Battery  
Type is applied to both battery banks. We strongly recommend against designing  
systems using both liquid and gel cells as their charging requirements are quite different.  
The default value is Type #1, a liquid electrolyte lead acid battery. To select Type #2,  
(gelled electrolyte lead acid batteries) set TYPE to 2. Changing the battery type sets an  
approximately appropriate Peukert rate compensation exponent (1.25 for liquid cells and  
1.11 for gel cells). When type 1 is selected, a Charged Voltage of 13.2 (or 26.4 V) is  
selected, while Type 2 sets a default Charged Voltage of 13.5 (or 27 V). You may wish to  
select a different Charged Voltage. See Temperature Compensation Table on page 17.  
19  
 
F11 - Not Used  
F12 - Not Used  
F13 - Not Used  
F14 - DISPLAY TEST  
DEFAULT: OFF  
RANGE: ON when SET button is depressed when  
this function is active.  
OFF when SET is released.  
This function confirms proper operation of the Link 20 front panel display. When  
the SET button is pressed in the F14 mode, the two top left lights on the battery light bar  
willbeanorange/yellowcolor.Allotherlightswilldisplaytheirnormalcolorandthenumeric  
displaywillread-188.8.ThedisplaywillreturntonormalwhentheSETbuttonisreleased.  
Operation of the two right (green) lights on the battery light bar is confirmed when power  
is initially applied to your Link 20.  
F15 - DISPLAY SOFTWARE REVISION NUMBER  
Function F15 selects display of the software revision number. This number is used  
internally with Xantrex Technology tokeep track of which version of software is installed  
in your Link 20. This number should be written down in the Setup table contained in this  
manual for your future reference.  
20  
 
THIS PAGE INTENTIONALLY BLANK  
21  
 
HOW TO RESET YOUR UNIT  
RESET: Two types of RESET are provided:  
Resetting of amp hours to zero or a complete reset  
of all parameters to factory default settings.  
To access the RESETfunctions:  
Before you begin, select the battery you wish to reset. To reset both batteries,  
you'll need to go through the reset procedure twice, once for each battery.  
1)  
2)  
3)  
4)  
Hold down the SET button until SEL appears in the numeric display.  
Press the SEL button five times until the red light above the word RESET appears.  
AH is shown in the numeric display.  
If you wish to reset amp hours, simply press and hold the SET button for five  
seconds. When amp hours are reset, the word ALL is displayed, warning that you  
are about reset ALL settings to the factory defaults.  
5)  
If you hold SET five more seconds, all factory default settings will be restored.  
Resetting amp hours to zero does not eliminate historical battery data.  
However, if you reset ALL, you will remove any battery history you have accumulated.  
This reset function would be the one to use when you install a new set of batteries,  
for example.  
22  
 
DATA: YOUR BATTERY HISTORY  
DATA: The DATA mode is used to recall key  
historical information about the battery.  
To access the DATAdisplays:  
Before you begin, select the battery whose data you wish to see.  
1)  
2)  
3)  
4)  
5)  
6)  
7)  
Hold down the SET button until SEL appears in the numeric display.  
Press the SEL button six times until the red light above the word DATA appears.  
Charging Efficiency Factor is the first number displayed.  
Press SEL again. The number of CEF Recalculations is displayed.  
Press SEL again. The deepest depth of discharge is displayed.  
Press SEL again. The average depth of discharge is displayed.  
Press SEL again. The next light on the Light Bar, the one over the word LOCK  
will come on. The LOCK function is described on the next page.  
What the Historical Information Means:  
CEF (Displayed as E99): The Charging Efficiency Factor (CEF) is the rate at which amp  
hours are counted back up during charging. The amp-hour CEF, not kilowatt-hour CEF,  
isdisplayed.AdisplayofE99 indicatesa99%CEFbasedonamphours.The Defaultsetting  
is 95%. NOTE: If the CEF display has a "u" in front of it, this means the CEF has been  
selected by the user. See Advanced Function F06 on page 18 for details.  
#CEF Recalculations (Displayed as +I999): This is the number of times that the battery  
hasbeendischargedmorethan10%andthencompletelyrecharged(meaningchargeduntil  
theChargedParametershavebeenmet).Considerthistobe thenumberofcharge/discharge  
cycles the meter has recorded since its last RESETto factory defaults. A discharge of less  
than 10% of battery capacity is not counted as a "cycle."  
Deepest Discharge (Displayed as -i999): Shows the deepest discharge in amp hours  
recorded by the meter since its last RESETto factory defaults. Think of this as the "worst  
thing you've ever done to your battery."  
Average Discharge (Displayed as i999): The running average of all discharges since  
RESETto factory defaults. For best battery life, you should not routinely discharge more  
than50–65%ofyourbattery'scapacity.Ifyoudo,youshortenitslife.Anaveragedischarge  
of 500 amp hours on a 900 Ah battery is demanding but not unreasonable. An average  
discharge of 180 amp hours from a 200 Ah battery is almost a sure way to make a battery  
salesman happy!  
23  
 
LOCK: KID-PROOFING  
LOCK: The LOCK mode is used to keep children  
(or others) from changing your Link 20 Setup.  
To access the LOCK:  
1)  
2)  
3)  
5)  
Hold down the SET button until SEL appears in the numeric display.  
Press the SEL button 10 times until the red light above the word LOCK appears.  
Press SET. The word ON or OFF will appear in the numeric display.  
Press SET again to change LOCK status.  
24  
 
SETTING PEUKERT EXPONENT  
When you select Battery Type (See Function F02 on Page 20), your Link 20 automati-  
cally sets a Peukert exponent which is generally correct. However, your batteries may  
have different characteristics than "average" and you may wish to change the exponent  
so your Time Remaining and Light Bar displays will be as accurate as possible. To  
change the Peukert exponent, proceed as follows:  
Before you begin, select the Battery you wish to apply the new  
exponent to: BAT 1 or BAT 2.  
A.  
Press and hold the SET button for 3 seconds to enter Setup mode. SEL appears  
LED is on.  
in the display. Press SEL and notice that the green  
B.  
Press SEL again and note that the  
light comes on. Continue to press the  
SEL button until F08 appears in the display. (This will require eighteen presses of the  
SEL button.) The right-most green light bar indicator with the legend FUNC under it will  
be lit.  
C.  
Now press and hold the SET button. If Battery Type is set to #1 (liquid cells), the  
default value of 1.25 (or the previously programmed value) will appear in the display. If  
Battery Type #2 (gel cells) is selected, the default value of 1.11 (or the previously pro-  
grammed value) will be displayed. The range of values is from 1.0 to 1.50.  
Holding down the SET button will cause the display to increment in 0.01 steps, after  
four increments the display scrolls faster. When the value you want appears, release the  
SET button. If you overshoot your capacity you will have to scroll all the way to 1.50  
after which the display will roll over to 1.00 and continue incrementing up.  
D.  
After 10 seconds, if no keys are pressed, the Link 20 exits the Setup mode and  
the selected value is stored as the new Peukert's exponent and the display returns to  
(volts).  
25  
 
HIGH DISCHARGE RATES  
& PEUKERT'S EQUATION  
Peukert's Equation describes the effect of different discharge rates on battery  
capacity. As the discharge rate increases the available battery capacity decreases. The  
tables and examples on the following pages illustrate this effect and how to use the table  
to estimate the exponent "n". The tables on pages 27 and 28 have typical values of "n"  
for common batteries.  
The Link 20 uses Peukert's equation in calculations to forecast the Time  
Remaining and run the light bars. The amp hours display is always the actual number of  
amp hours consumed. This means that if you heavily discharge a battery, your time-  
remaining display may show zero hours remaining before the expected number of amp  
hours of battery capacity is consumed.  
Making two discharge tests, one at a high discharge rate (to get I1[current] and  
t1[time]) and one at a low rate (to get I2[current] and t2[time]), that bracket your normal range of  
operation, allows you to calculate an "n" which will describe this varying effect. The  
Link 20 uses a default value of "n" equal to 1.25 which is typical for many batteries.  
At some low to moderate discharge rate, typically a battery's 20-hour rate, the  
logarithmic effect of Peukert's Equation is greatly reduced. The effect of discharge rates  
smaller than this is nearly linear. Battery manufacturer specifications of battery capacity  
in amp hours is typically given at the 20-hour rate. If a battery is discharged at, or slower  
than, the 20-hour rate, you should be able to remove the rated capacity if the battery  
is healthy.  
The equation for Peukert's Capacity (C ) is:  
p
log t2 - log t1  
n
n =  
C = I t where  
p
log I1 - log I2  
By doing two discharge tests and knowing I1 & I2 (discharge current in amps of  
the two tests), and t1 & t2 (time in hours for the two tests) you can calculate n (the  
Peukert exponent). You will need a calculator with a log function to solve the equation above.  
Instead of doing two discharge tests yourself, you may use the 20-hour discharge rate  
and the number of reserve minutes as the two discharges to solve Peukert's equation.  
See the example given on page 29. After you solve for your Peukert's exponent you may  
enter it using Advanced Function F08.  
26  
 
HIGH DISCHARGE RATES  
& PEUKERT'S EQUATION  
The table below may be used to understand the effect of high rates of  
discharge on available battery capacity. It may also be used to esti-  
mate the exponent "n" for a battery after a single discharge test. The  
table is based on a 100 Ah battery but may be used for any capacity  
battery by using an appropriately scaled current. See the examples  
below:  
PERCENTAGE OF AVAILABLE CAPACITY FROM A  
100 Ah BATTERY AT DIFFERENT DISCHARGE RATES  
USING DIFFERENT PEUKERT'S EXPONENTS  
DISCHARGE RATE IN AMPS  
n
5 10 16.7 25 50 75 100 150 200 250 300 400 500  
1
100 100 100 100 100 100 100 100 100 100 100 100 100  
1.1 100 93 88 85 79 76 74 71 69 67 66 64 63  
1.2 100 87 78 72 63 58 55 51 48 46 44 42 40  
1.25 100 84 74 67 56 51 47 42 40 37 36 33 32  
1.3 100 81 69 62 50 44 41 36 33 31 30 27 25  
1.4 100 76 61 52 40 34 30 26 23 21 20 17 16  
1.5 100 71 55 45 32 26 22 18 16 14 13 11 10  
Example #1: Assume you have a 200 Example #2: A 100 Ah bat-  
Ah battery and discharge it at the 50 tery with a Peukert's expo-  
amp rate until the battery reaches nent of 1.3 will deliver only  
1.75 V per cell (10.5 V for a 12 V bat- 41% of its capacity when  
tery). This is equivalent to a discharge supplying a 100 A load.  
rate of 25 A for a 100 Ah battery. If  
the battery delivered 67% (134 Ah)  
the appropriate Peukert's exponent  
would be 1.25.  
27  
 
TYPICAL PEUKERT'S EXPONENTS  
Typical Values for Peukert's Exponent "n"  
This table contains values for the exponent "n" for various batteries  
and manufacturers. They are calculated from the 20-hour rating and  
the Reserve Minutes @ 25 A as supplied by the manufacturer. They  
should be considered only a guide for selecting "n".  
Prevailer & SeaGel Batteries  
Model Volts  
8GGC  
8GU1  
8GU24  
8GU27  
8GU30H  
84D  
Res. Min.  
375  
20-Hr. Rating  
"n"  
1.14  
1.20  
1.13  
1.12  
1.12  
1.11  
1.10  
6
180  
43  
12  
12  
12  
12  
12  
12  
43  
130  
70  
167  
86  
188  
95  
388  
500  
180  
225  
8G8D  
Trojan Batteries  
Model Volts  
Res. Min.  
447  
20-Hr. Rating  
"n"  
1.24  
1.19  
1.14  
1.17  
1.21  
1.28  
1.23  
1.28  
1.27  
1.27  
1.17  
T-105  
T-125  
T-145  
J250  
6
6
6
6
225  
235  
244  
250  
305  
350  
85  
488  
530  
535  
660  
760  
135  
J305  
6
L16  
6
24TM  
27TM  
30XHS  
SCS225  
EV8D  
12  
12  
12  
12  
12  
160  
225  
225  
450  
105  
130  
130  
216  
28  
 
TYPICAL PEUKERT'S EXPONENTS  
Surrette and Rolls Batteries  
Model Volts  
Res. Min.  
345  
20-Hr. Rating  
"n"  
EHG-208  
EIG-225  
EIG-262  
24/90  
27/12M  
30H/108  
HT/4D  
6
6
6
12  
12  
12  
12  
12  
208  
225  
262  
90  
1.42  
1.54*  
1.72*  
1.16  
1.23  
1.08  
1.15  
1.20  
350  
395  
165  
190  
230  
348  
450  
112  
108  
170  
221  
HT/8D  
*Use Max allowed "n" of 1.50  
CALCULATING PEUKERT'S EXPONENT  
Example of using Reserve Minutes @ 25 amps  
and the 20-hour rate to calculate "n".  
First convert Reserve Minutes to hours, then find the discharge current  
at the 20-hour rating. Finally use a calculator to solve the arithmetic.  
Trojan T-105:  
Reserve Minutes = 447 min @ 25 amps.  
t1 = 447 min = 447/60 = 7.45 hrs  
I1 = 25 amps  
20 Hour rating = 225 Ah  
t2 = 20 hours  
I1 = 225 amp hours/20 hours = 11.25 amps  
log t2 - log t1  
log 20 - log 7.45  
log 25 - log 11.25  
1.301 - 0.872  
1.398 - 1.051  
=
n =  
= 1.24  
=
log I1 - log I2  
29  
 
SETUP & HISTORICAL DATA  
The following table is a summary of the major values that may be changed through  
Setuporbyaccumulatinghistoricaldata.Thecolumnontherightisprovidedtowritedown  
your setup values or historical data. Be sure and know these values before calling for  
customer service. Multiply values by two for 24-volt systems.  
PARAMETER DEFAULT  
Bat. 1 Bat.2  
_________ ________  
_________ ________  
_________ ________  
BATTERY VOLTSCHARGED  
BATTERY AMPSCHARGED  
BATTERY CAPACITY  
13.2 V  
2%  
200 Ah  
DATA  
Bat. 1 Bat.2  
CEF  
_________ ________  
_________ ________  
_________ ________  
_________ ________  
# OF CEF RECALC'S  
AVG DEPTH OF DISCHARGE  
DEEPEST DEPTH OF DISCHARGE  
FUNCTIONS  
DEFAULT  
Bat. 1 Bat.2  
DISPLAY SCAN (F01)  
DISPLAY SLEEP (F02)  
AMBIENT TEMP. (F03)  
Off  
_________ ________  
_________ ________  
_________ ________  
_________ ________  
_________ ________  
ON  
70 °F  
Ah/kWh  
(F04)  
(F05)  
(F06)  
Ah displayed  
Off  
ALT. ENERGY  
Manual CEF  
95% This value should  
only be set if you do NOT  
want your Link 20 to  
automatically calculate CEF _________ ________  
TEMP. COEF.  
(F07)  
0.5  
_________ ________  
_________ ________  
_________ ________  
_________ ________  
_________ ________  
PEUKERT EXP. (F08)  
DISCH. FLOOR (F09)  
BATTERY TYPE (F10)  
SOFTWARE REV. (F15)  
1.25  
100%  
#1 LIQUID LEAD ACID  
(Same for either battery)  
30  
 
READ BEFORE WIRING !!!!!  
Before wiring the Link 20, install the shunt as indicated.  
All wiring should be done before installing the meter power fuse.  
GENERALNOTES  
1) Wires used should be #16 or #18 AWG. (Larger wire is acceptable, but not necessary.)  
Wiring should be in accordance with the NEC, ABYC, or other applicable standards.  
2) The Shunt Sense Leads must be a twisted pair. Leads up to 250 feet long may be used  
if they are not run close to other noise-producing conductors and #16 AWG twisted pair  
wire is used. Offset error should be less than 0.2 amps.  
Fortheeasiestinstallationyoumaywishtopurchaseourfourtwistedpaircablewith  
the same color code as enclosed wiring diagram. This cable may be run between the meter  
and the batteries to supply all needed signals. This cable is available from your dealer or  
from Xantrex Technology in various convenient lengths. Xantrex Part Number 84-2014-  
00 is a 25' cable while Part Number 84-2015-00 is a 50' cable.  
Note: You may make your own twisted pair wire by chucking up two wires in an electric  
drill andtwistingthembyrunningthedrillmotoruntilthereare45twistsper inch.Awrap  
of tape every 16 inches will keep the wires together and make them easier to pull through  
holes and raceways.  
3) Caution! If your starter draws more than 500 amps see #5 below.  
CAUTION!!!!  
The output voltage of the shunt is very small. It is critical that all of the connections  
for the shunt sense leads have the highest possible integrity. Every effort must be  
made to prevent corrosion that might affect the sense leads.  
4) Battery current is sensed with a shunt which is a very precise, small, resistance. It is  
inserted in series (in line) in the negative wire of the battery (battery bank) you wish to  
measure. The current is measured by sensing the voltage drop across this resistance. The  
uses a 50 mV @ 500 amp shunt. When 500 amps flows through the shunt, there is a 50 mV  
drop across it. Thus 10 amps equals 1 mV or 1 amp equals 0.1 mV. The meter displays  
this small voltage as amps. If you wish to check this you will need a very accurate digital  
meter(Fluke87in41/2digitmodeorbetter)ifthecurrentisbelow30amps(3.0mV).Above  
50 amps most digital meters can be used for testing.  
5) Big Engine Note: If your starter current exceeds 500 amps for more than 10 seconds,  
asmaybethecasewithgasenginesofmorethan350cubicinchesordieselenginesofmore  
than 100 horsepower, you'll need to use either a heavy duty shunt or connect the starter  
negative directly to the battery side (BSHB) of the shunt so that starter current does not  
flowthrough it.Theproblemwithwiringsothatstartercurrentdoesn'tgothroughtheshunt  
isthatif thealternatorisofthegroundedcasetype, itschargingcurrentwillnotbeflowing  
through the shunt. The alternator ground must be isolated from the engine and run to the  
loadside(BSHG)ofthebatteryshunttobeabletomeasure thecurrentgoing intothebattery  
from the alternator. Isolated negative output alternators are available and we strongly  
31  
 
recommend them.With isolatednegativeoutputalternators,rememberthatinstrumentation  
and other loads grounded directly to the engine block will not be measured unless their  
negatives are relocated to the load side of the Battery Shunt.  
Special high current shunts are really the right solution and may be ordered from  
XantrexTechnologyInc. Aseparateenginestartingbatterywhosenegativeisconnected  
directly to the engine also solves the problem. The Xantrex Technology heavy duty shunt  
is Part Number 84-2013-00.  
6) Wehaveshownseveralwiresconnectedto theloadside ofthebatteryshuntinthewiring  
diagram. If more than a few wires must be connected here, it is best to use a 2/0 jumper  
from the shunt to a good negative bus. We recommend that no more than two, or at a  
maximum three, connections per large bolt be made on the negative bus side of the shunt.  
The negative bus should be a solid copper or brass bar with many threaded screws under  
which the negatives for all of the loads may be secured. It should be fed with a conductor  
of sufficient size so that there is no appreciable voltage drop even under full load.  
7) Wearefrequentlyaskedaboutbatteryisolators. Wedon'trecommendthem. Thereason  
is that battery isolators have a noticeable voltage drop across them which may be greater  
than 0.5 V. In most instances, a better solution is to use a battery combiner which keeps  
a starting battery charged without a voltage drop.  
32  
 
WIRE BY WIRE DETAIL  
BATTERYCOMPARTMENT  
The dual shunt is the current sensor for the Link 20. Its 50 mV @ 500 A rating means  
that when 500 amps flows through it, 50 mV is generated across it. The millivolt signal is  
translated into an amps display in the meter. For example: A 50 A load generates 5 mV  
across the shunt and would be displayed as 050 amps. Caution: In the diagram below,  
the darker wires represent primary wiring and should be able to carry full battery load  
current. Size appropriately!  
POSITIVE LEADS TO BATTERY SWITCH  
+
-
+
+
BAT. 1  
NO OTHER WIRES  
CONNECTDIRECT  
TOBATTERY!  
BAT. 2  
-
Dual Shunt  
50 mV @ 500 A  
2 amp fuses.  
Mount within  
7" of battery.  
2 amp fuse.  
Mount within  
7" of battery.  
ALLLOAD  
GROUNDS GO ON  
THIS SIDE OF  
SHUNT  
BLACK - GROUND  
DC SYSTEM  
NEGATIVE  
4 twisted pair cable  
to meter location  
Battery Compartment  
ABOUTTWISTEDWIRE:  
Westronglyurgeyoutousethe4twistedpaircableavailablethroughyourXantrexdealer  
inordertoconformtothewirecolorsshownonthisdiagram.Usingstandardwirecolors  
allows us to do a much better job of troubleshooting and will aid you should a problem  
developfour,five,even10yearsfromtoday.Ifyouarenotabletoobtainthiswire,make  
suretheshuntsenseleadpairs(Orange&Green,Yellow&Brown)aretwisted45twists  
per inch. Twisted shunt wires minimize noise and ensure reliable current readings.  
33  
 
WIRING CONNECTIONS TO  
THE Link 20  
Make the necessary wire connections to the Link 20  
as shown in the following diagram:  
CAUTION  
Use correct-sized screwdriver for terminal  
screws. Tighten firmly but do not over-tighten  
to avoid damage.  
REAR VIEW OF  
LINK 20  
NOTE: The screw terminals are small.  
During assembly and testing, the screw ter-  
minals are tightened. To accommodate wires,  
loosen the screws until flush with the top of  
the terminal strip and pry open the wire clamp  
with a paper clip. The holes will accept 16  
AWG wire IF you have a clean cut, clean  
strip and twist the wires tightly. Use needle-  
nosed pliers to insert the wires.  
NOTE: BE SURE TO  
1
USE TWISTED WIRE FOR  
GREEN & ORANGE  
2
AND YELLOW & BROWN  
SHUNT SENSE PAIRS.  
3
4
5
4 twisted pair cable  
6
7
8
Meter Location  
[1] DC - Meter Negative (BLACK)  
[2] Bat. 1 Shunt Sense Load Side (GREEN)  
[3] Bat. 1 Shunt Sense Battery Side (ORANGE)  
[4] Bat. 1 Voltage Sense (0.1–50 V DC) (BLUE)  
[5] DC + Meter Power (9–40 V DC) (RED)  
[7] Bat. 2 Voltage Sense (0.1–50 V DC) (VIOLET)  
[6] Bat. 2 Shunt Sense Battery Side (YELLOW)  
[8] Bat. 2 Shunt Sense Load Side (BROWN)  
34  
 
WIRE-BY-WIRE CHECK  
Most failures and problems are due to wiring errors. Please double check the wiring.  
(Color code shown is for Xantrex cable)  
# 1 - DC Power (Black Wire). Start at terminal #1 of the and follow it to the big  
bolt on the Load side of the shunt. Do not connect this wire to the small screw  
terminal with the Green shunt sense lead.  
# 2 Shunt Sense Lead Load Side (Green Wire). This wire connects to the small  
screw on the Load ("house") side of the shunt. This wire must be a twisted pair  
with the Orange wire described below. To check this wire start at Link 20 termi-  
nal #2 and follow it to the small screw on the Load side of the shunt. There  
should be no other wires connected to this screw.  
Note: Now is a good time to check the primary wiring from the shunt to the  
battery. There should be only one heavy cable from the Battery side of the shunt  
to the battery. All loads and sources must be connected on the other side of the  
shunt. Only the shunt may be connected directly to battery negative!  
# 3 Battery Side of Shunt (Orange Wire). This wire must be a twisted pair with  
the Green wire described above. To check this wire, start at terminal #3 and follow  
it to the small screw on the Battery side of the shunt. There should be no other  
wires connected to this screw.  
# 4 Voltage Sense Wire (Bat.+) (Blue Wire). From terminal #4 this wire should run  
to a 2 amp fuse holder, located within 7" of the battery. The other side of the fuse  
holder should go to the positive (+) battery post.  
# 5 Link 20 Meter Power (Bat.+) (Red). From terminal #5 this wire should run to  
a 2 amp fuse holder, located within 7" of the battery. The other side of the fuse  
holder should go to the positive (+) battery post. This is a separate wire from #4  
above (although they go to the same place) because we do not want even the small  
voltage drop from meter power to affect the Link 20 voltage sense measurement.  
# 6 Second Battery Voltage Sense (Bat#2+) (Violet). From terminal #6 this wire  
should run to a 2 amp fuse holder, located within 7" of the second (starting)  
battery. The other side of the fuse holder should go to the positive (+) battery  
post.  
# 7 Battery 2 Shunt Sense Battery Side (Yellow). From terminal #7 this twisted  
wire runs to the Battery 2 side of the dual shunt.  
# 8 Battery 2 Shunt Sense Load Side (Brown). From terminal #8 this wire should  
run the load side of Battery 2.  
35  
 
MOUNTING  
Surface mounting (Recommended method). Your Link 20 is supplied  
with a nesting-type mounting place which allows suface mounting using our  
exclusive Thin-Mount technology.  
Looking at nesting plate as it mounts on wall  
Pan head screws go here  
Countersunkscrewsgohere  
The phone cord to the Freedom inverter  
and the wires to the battery compartment  
may be led out the back of the nesting  
receptacle...  
...or they may be led down from the  
bottomofthenestingreceptacle.Nomatter  
which routing you choose, be sure to use  
strain relief on both wires.  
36  
 
REMOVING THE UNIT  
To demount the Link 20 from the nesting receptacle, insert a small coin, knife blade,  
or small screwdriver blade and press inward while gently pulling the meter away  
from the nest.  
Press in on this tab with a thin metal  
coin while pulling one side of the unit  
away from the nesting receptacle.  
37  
 
START UP  
Once you have completed ALL instructions on page 35, insert the voltage sense  
wire fuses (Blue Wire to fuse holder on battery #1, Violet Wire to fuse holder on battery  
#2).  
LAST, install the meter power fuse—Blue and Violet wire fuses first, RED wire  
fuse LAST! The fuse should be in a fuse holder and should be connected in a smooth  
motion. A "ragged" power up may cause a meter lock up. Both light bars and the digital  
display should come on. The display will be flashing on initial power up.  
Factory Default Settings  
The LINK 20 comes on in the  
(volts) mode with the display flashing to indicate that  
it has been powered up from the de-powered state. Left untouched for 10 minutes, the  
LINK 20 will go to "sleep", turning off the numeric display leaving only the two light bars  
on. This is a power-saving feature. Touching either the SEL or SET buttons will return  
the LINK 20 to the function it was in when it went to "sleep."  
The LINK 20 is designed to work "out of the box." The factory default values are  
appropriate for a moderate capacity 12 V liquid lead acid battery and a typical user  
display and function setup. Often, the only change that must be made is setting the  
battery capacity. You may also have to set the battery type and an appropriate Peukert's  
exponent.  
LINK 20 factory default settings are:  
1.  
2.  
3.  
4.  
Automatic Scanning of V, A, Ah, and time is OFF for both batteries.  
Sleep Mode is ON. This turns the digital numeric display off after 10 min.  
Charge Efficiency Factors (CEFs) equal 95% and learn CEF mode is on.  
Charged Parameters: Voltage = 13.2, Charged Current = 2%. The battery  
must exceed 13.2 V and the current must be less, in amps, than 2% of  
declared capacity for five minutes to consider the battery full.  
Battery capacities both set to 200 amp hours.  
5.  
6.  
Peukert Exponents = 1.25.  
38  
 
WARRANTY  
What does this warranty cover?  
This Limited Warranty is provided by Xantrex Technology, Inc. (“Xantrex”) and covers defects in  
workmanship and materials in your Xantrex Link 20 Battery Monitor. This warranty lasts for a Warranty  
Period of 12 months from the date of purchase at point of sale to you, the original end user customer.  
This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty  
Period.  
What will Xantrex do?  
Xantrex will, at its option, repair or replace the defective product free of charge, provided that you notify  
Xantrex of the product defect within the Warranty Period, and provided that Xantrex through inspection  
establishes the existence of such a defect and that it is covered by this Limited Warranty.  
Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building  
replacement products. Xantrex reserves the right to use parts or products of original or improved design in the  
repair or replacement. If Xantrex repairs or replaces a product, its warranty continues for the remaining  
portion of the original Warranty Period or 90 days from the date of the return shipment to the customer,  
whichever is greater. All replaced products and all parts removed from repaired products become the property  
of Xantrex.  
Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a  
Xantrex-selected non-expedited surface freight within the contiguous United States and Canada. Alaska and  
Hawaii are excluded. Contact Xantrex Customer Service for details on freight policy for return shipments  
outside of the contiguous United States and Canada.  
How do you get service?  
If your product requires troubleshooting or warranty service, contact your merchant. If you are unable to  
contact your merchant, or the merchant is unable to provide service, contact Xantrex directly at:  
Phone:18006700707(tollfreeinNorthAmerica)16044222777(direct)  
Fax:16044202145  
Direct returns may be performed according to the Xantrex Return Material Authorization Policy described in  
your product manual. For some products, Xantrex maintains a network of regional Authorized Service Cen-  
ters. Call Xantrex or check our website to see if your product can be repaired at one of these facilities.  
In any warranty claim, dated proof of purchase must accompany the product and the product must not have  
been disassembled or modified without prior written authorization by Xantrex.  
Proof of purchase may be in any one of the following forms:  
The dated purchase receipt from the original purchase of the product at point of sale to the end user, or  
The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM) status, or  
The dated invoice or purchase receipt showing the product exchanged under warranty  
What does this warranty not cover?  
This Limited Warranty does not cover normal wear and tear of the product or costs related to the removal,  
installation, or troubleshooting of the customer’s electrical systems. This warranty does not apply to and  
Xantrex will not be responsible for any defect in or damage to:  
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either  
internally or externally, or damaged from improper use or use in an unsuitable environment;  
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input  
voltage that creates operating conditions beyond the maximum or minimum limits listed in the Xantrex  
product specifications including high input voltage from generators and lightning strikes;  
c) the product if repairs have been done to it other than by Xantrex or its authorized service centers  
(hereafter “ASCs”);  
d) the product if it is used as a component part of a product expressly warranted by another manufacturer;  
e) the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or  
removed.  
39  
 
Disclaimer  
Product  
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH  
YOUR XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS,  
GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE  
IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES  
OF MANUFACTURER’S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT  
RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR  
A
PARTICULAR PURPOSE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE TO  
A
THE EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO  
THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY.  
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL  
DAMAGES, LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING WITHOUT  
RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO PROPERTY, ANY PERSONAL INJURY, ANY  
DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION,  
INTEGRATION OR OPERATION OF THE PRODUCT.  
Exclusions  
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the  
extent you are entitled to implied warranties under federal law, to the extent permitted by applicable law they  
are limited to the duration of this Limited Warranty. Some states and provinces do not allow limitations or  
exclusions on implied warranties or on the duration of an implied warranty or on the limitation or exclusion of  
incidental or consequential damages, so the above limitation(s) or exclusion(s) may not apply to you. This  
Limited Warranty gives you specific legal rights. You may have other rights which may vary from state to  
state or province to province.  
Warning: Limitations On Use  
Please refer to your product user manual for limitations on uses of the product. Specifically, please note that  
the Xantrex Link 20 Battery Monitor is not intended for use in connection with life support systems and  
Xantrex makes no warranty or representation in connection with any use of the product for such purposes.  
Return Material Authorization Policy  
Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA)  
number and the correct factory “Ship To” address. Products must also be shipped prepaid. Product shipments  
will be refused and returned at your expense if they are unauthorized, returned without an RMA number  
clearly marked on the outside of the shipping box, if they are shipped collect, or if they are shipped to the  
wronglocation.  
When you contact Xantrex to obtain service, please have your instruction manual ready for reference and be  
prepared to supply:  
The serial number of your product  
Information about the installation and use of the unit  
Information about the failure and/or reason for the return  
A copy of your dated proof of purchase  
40  
 
Return Procedure  
1. Package the unit safely, preferably using the original box and packing materials. Please ensure that your  
product is shipped fully insured in the original packaging or equivalent. This warranty will not apply where  
the product is damaged due to improper packaging.  
2. Includethefollowing:  
The RMA number supplied by Xantrex Technology Inc clearly marked on the outside of the box.  
A return address where the unit can be shipped. Post office boxes are not acceptable.  
A contact telephone number where you can be reached during work hours  
A brief description of the problem  
3. Ship the unit prepaid to the address provided by your Xantrex customer service representative.  
If you are returning a product from outside of the USA or Canada  
In addition to the above, you MUST include return freight funds and are fully responsible for all documents,  
duties, tariffs, and deposits.  
If you are returning a product to a Xantrex Authorized Service Center (ASC)  
A Xantrex return material authorization (RMA) number is not required. However, you must contact the ASC  
prior to returning the product or presenting the unit to verify any return procedures that may apply to that  
particularfacility.  
41  
 
LINK 20 SPECIFICATIONS  
Power Supply Voltage  
Power Consumption  
8–40 volts DC (Do not power with a 32 V system!)  
90* mA (Typical) 170 mA (Full display brightness)  
25* mA (Sleep mode; light bar only on.)  
* @12 VDC. Values are about half on 24 V systems.  
Voltage Measurement Range 0.1–50 volts DC  
VoltageResolution  
0 to 19.95 V (0.05 V resolution)  
20.0 to 50.0 V (0.1 V resolution)  
Voltage Accuracy  
+ (0.6% of reading + 1 least count of resolution)  
Current Measurement Range + 500 amps DC  
Current Resolution  
0.1 amp DC (From 0 to + 42.0 amps)  
1 Amp DC (From + 42 to + 500)  
Current Accuracy  
Current Shunt  
+ (0.8% of reading + 1 least count of resolution)  
Ratio: 50 mV @ 500 A  
Amp Hour Range  
TimeRemainingRange  
ChargerVoltageRegulation  
Product overall size:  
Weight:  
+ 1,999 amp hours  
255 hours maximum  
+ 0.2 volts DC  
4.725" x 2.975'' x 1.075" deep  
Approx. 4.6 oz. (excluding current sensing shunt)  
43  
 
Xantrex Technology Inc.  
Toll free 1 800 670 0707  
Direct 1 604 422 2777  
Fax 1 604 420 2145  
445-0196-01-01 Rev. 1  
Printed in the U.S.A.  
 

Whirlpool Convection Oven GBS277PRB01 User Manual
Whirlpool Ice Maker CHE 12RC User Manual
Whirlpool Microwave Oven YKHMS145J User Manual
White Rodgers Welding System 37 1119B User Manual
Wibur Curtis Company Coffeemaker C500AP User Manual
Winegard TV Antenna HD7698P User Manual
Woods Equipment Power Roller VR48A User Manual
Xerox Scanner xerox mobile scanner pc connect User Manual
Zanussi Freezer 726318 User Manual
Zephyr Ventilation Hood Z1C 00LL User Manual